AB 触摸屏中文文本显示

2018-02-07 6页 doc 50KB 158阅读

用户头像

is_511210

暂无简介

举报
AB 触摸屏中文文本显示AB 触摸屏中文文本显示 1. 首先,如果使用的是FT6.0以上的人机界面软件,就必须通过U盘或者CF卡将字库文件拷贝到触摸屏中。如何拷贝呢,您 需要在U盘(有时会不认U盘,请多试几个U盘)或者CF卡中根目录下建立一个名字为”Fonts”的文件夹,然后将字库文件 拷贝到这个目录下,然后插入人机界面后面的插口中。在人机界面中,点击“Terminal Settings” --- “File Management” --- “Copy Files” --- “Copy Fonts” ---- “External Storage ...
AB 触摸屏中文文本显示
AB 触摸屏中文文本显示 1. 首先,如果使用的是FT6.0以上的人机界面软件,就必须通过U盘或者CF卡将字库文件拷贝到触摸屏中。如何拷贝呢,您 需要在U盘(有时会不认U盘,请多试几个U盘)或者CF卡中根目录下建立一个名字为”Fonts”的文件夹,然后将字库文件 拷贝到这个目录下,然后插入人机界面后面的插口中。在人机界面中,点击“Terminal Settings” --- “File Management” --- “Copy Files” --- “Copy Fonts” ---- “External Storage 1/2” --- 选中字体文件,然后选择“Destination”是 ”Internal Storage”. 2. 在Rsview Studio中下载字库simsun_2_50.ttc到PVC, 3. 在Configuration Mode, 进入 Terminal Settings/Font Linking. 4. 发现列中Arial font. 5. 点击 "Show Links" 键. 6. 点击 "Edit Link" 键. 7. 浏览 main font, 在列表中选择Simsun. 8. 点击 "Add Font" 键. 53463 - Max PanelView Ethernet Connections to MicroLogix How many PanelView Standard / PanelView Plus / PanelView Component can be connected to the Ethernet port of a MicroLogix controller? While the practical limit is two PanelViews per MicroLogix 1100, it is possible to go up to: 3 PanelView Plus connected to the ML1100. This is due to the connection limitations. Each PanelView Plus can potentially use five connections. The MicroLogix 1100 supports 16 incoming connections and 16 outgoing connections. 3 PanelView Standard will work just fine with the Ethernet port on the ML1100. PanelView Standard can use up to four connections. Although you can use up to four PV standard, if you use all four, you will not be able to get online via Ethernet as all of the possible connections would be used. The PanelView Component consumes one Ethernet connection, but the practical limit is 2:1: , 2 PVc per MicroLogix 1100 , 2 MicroLogix 1100 per PVc 63165 - PanelView Plus Compact Machine Edition Applications Limitations What are PanelView Plus Compact Machine Edition Applications Limitations? Compact Machine Edition Applications Compact Machine Edition applications are applications intended to run on the PanelView Plus Compact terminal. Compact Machine Edition applications have the following restrictions: , A maximum of 25 displays. , A maximum of 200 alarm messages. , A maximum screen resolution of 640x480. , Only available in 4, 6, and 10" screen sizes. , Only one RSLinx Enterprise shortcut; if no RSLinx Enterprise shortcut is defined, a single KEPServer Enterprise data server can be used to communicate with a single device. , o The Kepware Hilscher Universal and Modbus Plus communications drivers are not supported for PanelView Plus Compact terminals. , Only serial and Ethernet communications; if the application uses RSLinx Enterprise, only Serial-DF1, Serial-DH485 and Ethernet drivers are supported. , Only RSLinx Enterprise version 5.20 or later and FactoryTalk View Machine Edition version 5.1 or later supported. , FactoryTalk ViewPoint not supported. 55149 - How to use Global Connections Current Screen Number for PLC screen navigation on the PVc? How can the PLC cause the PVc to change screens? Assign a external tag to the read and write fields in Tags/Global Connections tab. At runtime the PVc will write the current screen number to the write tag (Destination Tag ) in the PLC. The PVc will read from the read tag ( Source Tag ) which will allow the PLC to control screen changes. The operator does not have control over screen changes until the read tag has a value of 0 (zero). Please allow time for screens to draw on screen changes before changing again. 21321 - How to change screens in RSView Machine Edition from a remote location.. Application Note: To change to a specific screen from a remote PLC, a tag must be selected in the 'Global Connections' / 'Remote Display Number' field. A (screen) number, written to this tag, will initiate the change to the appropriate screen. The number of the active screen will be reflected in the tag assigned to the 'Display Number' field. The value of the 'Display Number' field can be used as an acknowledgement to the PLC. Additional Notes: If a value other than 0 is left in the 'Remote display number' field, manual changing of screens will not be possible, the PLC will maintain control of screen changes. If manual screen changes are desired along with PLC control, the value of the 'Remote display number' field must be reset to 0. This can be done by writing a 0 to the tag from the PLC after an acknowledgement of a screen change. Another method could be to use a startup macro for each display that resets the 'Remote display number' tag to 0. If using a pushbutton from an HMI to change screens, there will be an additional 1 second delay. (approx.) Only 'Replace' type displays can be changed remotely because the 'On Top' display type cannot be assigned a display number. Summary: This technote describes methods for changing screens in Machine Edition, from a remote location. ie: PLC, HMI, etc.
/
本文档为【AB 触摸屏中文文本显示】,请使用软件OFFICE或WPS软件打开。作品中的文字与图均可以修改和编辑, 图片更改请在作品中右键图片并更换,文字修改请直接点击文字进行修改,也可以新增和删除文档中的内容。
[版权声明] 本站所有资料为用户分享产生,若发现您的权利被侵害,请联系客服邮件isharekefu@iask.cn,我们尽快处理。 本作品所展示的图片、画像、字体、音乐的版权可能需版权方额外授权,请谨慎使用。 网站提供的党政主题相关内容(国旗、国徽、党徽..)目的在于配合国家政策宣传,仅限个人学习分享使用,禁止用于任何广告和商用目的。

历史搜索

    清空历史搜索