SIMATIC PDM V6.0
Getting Started Edition 12/2004
Copyright Siemens AG 2004 All rights reserved
The reproduction, transmission or use of this document or its
contents is not permitted without express written authority.
Offenders will be liable for damages. All rights, including rights
created by patent grant or registration of a utility model or design,
are reserved.
Siemens AG
Bereich Automation and Drives
Geschaeftsgebiet Industrial Automation Systems
Postfach 4848, D- 90327 Nuernberg
Disclaimer of Liability
We have checked the contents of this manual for agreement with the
hardware and software described. Since deviations cannot be precluded
entirely, we cannot guarantee full agreement. However, the data in this
manual are reviewed regularly and any necessary corrections included in
subsequent editions. Suggestions for improvement are welcomed.
© Siemens AG 2004
Technical data subject to change.
Siemens Aktiengesellschaft A5E00325950-01
The Process Device Manager - Getting Started
A5E00325950-01 1-1
1 First Steps with SIMATIC PDM
What are you going to learn?
The following practical exercise will show you how simple it is to create a network
configuration and subsequently process the devices in SIMATIC PDM.
In this example, you will create a SIMATIC PDM configuration with devices. Later
on, you are going to work with the sensor "SITRANS P DS" from the Siemens
SITRANS P family.
Detailed instructions will lead you step-by step through the creation of a network
and SIMATIC PDM operation.
1.1 Creating a Project
Starting the Program
Start the program with a click the "SIMATIC Manager" desktop icon. An almost
empty window opens with a toolbar in the upper section (the number of icons in the
tool bar depends on whether you are using the integrated version or not).
First Steps with SIMATIC PDM
The Process Device Manager - Getting Started
1-2 A5E00325950-01
Creating a Project
Proceed as follows in order to create a project:
1. Select the menu command File > New.
2. Enter a name for the project (such as "PDM_1") in the displayed dialog box.
Verify that the "Project" and not the "Library" option is selected.
3. Confirm by clicking "OK".
First Steps with SIMATIC PDM
The Process Device Manager - Getting Started
A5E00325950-01 1-3
4. The new project task window "PDM_1" is displayed. Double-click the
"Networks" icon in the right-hand screen section. After this, the left-hand
screen section will be shifted over.
First Steps with SIMATIC PDM
The Process Device Manager - Getting Started
1-4 A5E00325950-01
Selecting the View in the SIMATIC Manager
You can choose between the following views:
The Component View is used for configurations in HW Config.
The Process Device Network View shows the process devices grouped
according to their network topology. You can configure process devices in this
Process Device Network View.
The Process Device Plant View provides a quick overview of the configured
process devices. You can configure devices without any network assignment.
NOTE: You can make a setting that determines which view is displayed when the
SIMATIC Manager is opened. If you use HW Config when configuring, we
recommend that the component view be made the default view. If you are using
the standalone version of SIMATIC PDM or are configuring the networks in the
SIMATIC Manager, you should make the Process Device Plant View the default
view. To set the default, select the menu command Options > Settings. In the
dialog box that is displayed, go to the "View" tab and select the desired view.
First Steps with SIMATIC PDM
The Process Device Manager - Getting Started
A5E00325950-01 1-5
Adding the HART Modem and Assigning the COM Port
1. To add a HART modem, right-click the "Network" icon and select the menu
command Insert New Object... > HART Modem. The PC is automatically
added and set up.
2. Double-click the PC, select the COM port in the right-hand section of the
window, and then right-click "Object Properties".
3. In the dialog box displayed, go to the "Connection Data" tab and select the
correct "COM Port" ("2" in our example).
4. Confirm your settings with "OK".
First Steps with SIMATIC PDM
The Process Device Manager - Getting Started
1-6 A5E00325950-01
Inserting HART Devices
You can insert up to 4 devices per project using the standard version of
SIMATIC PDM. If you need to configure more devices than that for a project, you
will have to purchase the expansions required to do this.
To insert the desired HART devices, proceed as follows:
1. Right-click the HART modem and in the context-sensitive pop-up menu select
the command Insert New Object…. > HART Device.
2. The dialog box "Insert SIMATIC PDM device Object(s)" is displayed.
3. In the "Name" field, enter the desired name for the HART device (in our
example HART_1).
Note: If have an option of 128 tags or more, the change log is also active. All
changes to a project are recorded in this log. In addition, a dialog box is displayed
in which you are prompted to enter comments on changes.
4. Confirm your entries with "OK". The program adds a device named "HART_1
1" to the project. The device is inserted in the right-hand section of the window.
First Steps with SIMATIC PDM
The Process Device Manager - Getting Started
A5E00325950-01 1-7
5. Double-click the device that you have just created. The SIMATIC PDM
application is opened. In the dialog box that is displayed, select whether you
want to work as a "Maintenance Engineer" or "Specialist". Confirm your
selection with "OK".
6. The "SIMATIC PDM Device Selection" dialog box is displayed. Now select your
HART device type. If it is not available, you can install the desired device at
this time. To do so, click the “Device Catalog” button. In the dialog box that is
then displayed, navigate to the folder containing the device catalog. Now select
the HART device type.
7. Confirm your selection with "OK".
Note: This process may take a few minutes. All current device descriptions (.DDLs)
will be loaded. Updates can be downloaded form the following Siemens website
(address current as of May 2000):
http://www.feldgeraete.de/76/produkte/simatic_pdm/infos.html
First Steps with SIMATIC PDM
The Process Device Manager - Getting Started
1-8 A5E00325950-01
Selecting a Sensor
To select a sensor, proceed as follows:
1. Double-click one of the sensors which you have inserted (such as on HART_1
1 in the example).
2. Select Sensors > Pressure > SIEMENS > SITRANS P-DS > Pressure > 16
Bar menu command to choose the appropriate sensor. Configure any other
devices you have selected for your project in the same manner.
3. After you have made your selections, confirm them with "OK".
First Steps with SIMATIC PDM
The Process Device Manager - Getting Started
A5E00325950-01 1-9
4. SIMATIC PDM is opened.
First Steps with SIMATIC PDM
The Process Device Manager - Getting Started
1-10 A5E00325950-01
1.2 Setting the Programming Device (PG)/PC Interface for
PROFIBUS Communication
When you create a PROFIBUS network, you should also make the settings for the
programming device (PG)/PC. To do so, proceed as follows:
1. In the SIMATIC Manager, select the Options > Set PG/PC Interface menu
command (in the standalone version the PG/PC interface is located in the
system Control Panel).
2. Select the CP that is installed in your device.
Note: The "Set PG/PC Interface" function is important if you want to create a
PROFIBUS system and configure PROFIBUS devices. SIMATIC PDM can be
used for HART systems as well as for PROFIBUS systems, although each
system does require different hardware (for example, for PROFIBUS systems
you will need a Siemens CP5611 or CP5511 card or another, equivalent card).
3. Confirm your settings with "OK".
First Steps with SIMATIC PDM
The Process Device Manager - Getting Started
A5E00325950-01 1-11
1.3 Configuring a Device
Start SIMATIC PDM by double-clicking the device symbol in the
SIMATIC Manager. In the dialog box that is then displayed, select the "Specialist"
or "Maintenance Engineer" option. Confirm your selection with "OK". The
SIMATIC PDM logo is now displayed.
SIMATIC PDM is now opened for the HART device that you selected. The values
displayed in the right-hand section of the window are not "current" values but come
from the DDL that you selected. To obtain the current values for your device, select
the Device > Upload to PG/PC menu command or click the corresponding button
in the toolbar.
First Steps with SIMATIC PDM
The Process Device Manager - Getting Started
1-12 A5E00325950-01
Caution: Before downloading data to a device, you should connect the software to
the HART device via the HART modem and upload the data currently in the device
to your PC.
To do this, select the Device > Upload to PG/PC menu command or click the
corresponding button in the toolbar. The on-screen values are replaced by the
actual values for the device. In the status bar, the status changes from "Not
connection" to "Connected". If you edit these values, their status changes from
"Initial value" or "Uploaded" to "Changed". To transfer the data to the sensor, select
the menu command Device > Download to Device or click the corresponding
button in the toolbar. All previous sensor data will be overwritten with your edited
data. Therefore, be sure to verify the correctness of all data before you transfer it to
the device.
First Steps with SIMATIC PDM
The Process Device Manager - Getting Started
A5E00325950-01 1-13
Note: It is possible that the HART device is not integrated in your version of
SIMATIC PDM. If this is the case, then please contact a Siemens representative at
the appropriate Siemens business office or service partner.
To find the appropriate contact person, please go to:
http://www.siemens.com/automation/partner
Congratulations! You now have worked through this "Getting Started" and
become acquainted with important terms, procedures and functionalities of
SIMATIC PDM. You are now ready to create your first project.
Should you encounter problems finding information on certain functions or
operating sequences for SIMATIC PDM or should you forget required command
sequences, please refer to our extensive Help on SIMATIC PDM.
We wish you a lot of success with your future projects!
Siemens AG
First Steps with SIMATIC PDM
The Process Device Manager - Getting Started
1-14 A5E00325950-01
Title
1 First Steps with SIMATIC PDM
1.1 Creating a Project
1.2 Setting the Programming Device (PG)/PC Interface for PROFIBUS Communication
1.3 Configuring a Device