Feb 2007
Product specifications are subject to change without notice
for close integration of
IS circuits into process-
connected systems
MTL4500 SERIES
Based on proven IS isolation technology,
MTL4500 Series modules do not need a high
integrity earth and the associated circuits can be left
floating or be earthed at any one point in
accordance with good earthing practices. MTL4500
Series provides single channel single loop integrity
across the range with the addition of dual channel
options for the switch/proximity modules, analogue
inputs and analogue outputs. There is even a quad
channel switch/proximity input module for the
maximum channel density.
Line fault detection (LFD) facilities are provided
across the range of I/O functions; on the
switch/proximity detectors, the MTL4523
solenoid/alarm driver and the isolating drivers.
Analogue input units such as the MTL4541 provide
line fault detection by repeating o/c or s/c currents
to the safe-area control system.
System backplanes are located in safe areas
and, because the hazardous-area circuits are
connected directly to the modules, do not need to be
certified. See MTL series backplanes, enclosures and
accessories for full details.
The easy migration from MTL4000 supports
existing installations because MTL4500 modules can
be mounted on backplanes that were designed for
MTL4000. A simple modification uses the backplane
mounting holes of the MTL4000 to accept the
mounting clips for the MTL4500 modules. This
ensures continued availability and operation of
process plant with new I/O modules and enhanced
functionality.
The MTL4500 Series of isolating interface units
introduces key concepts for integrating intrinsic
safety into large or medium sized process-connected
systems. Being exceptionally compact, the units give
high packing densities and plug into system
backplanes with safe-area connections made by
multiway connectors – an approach which not only
simplifies engineering but also reduces installation
and maintenance costs. MTL4500 modules are held
on the backplane with plastic clips that are simple to
use, secure in operation and avoid the use of screws,
giving further reduction in installation and
maintenance time and cost.
Input and output modules handle normal
process applications covering on/off or analogue
signals between hazardous-area equipment and
safe-area systems. Modules incorporate proven
intrinsically safe isolation techniques, internationally
certified for protecting equipment and wiring in all
zones and explosive atmospheres. Input, output and
power-supply circuits are isolated from each other,
giving maximum flexibility for control loop
applications.
Key module design features include a multiway
connector to the backplane for safe-area and power
supply connections. Hazardous-area connections
simply plug into the front of the module; this simplifies
installation and maintenance and reduces time, cost,
and the risk of errors. Status LEDs, configuration
switches and ports are located on the top or side of
individual modules for easy access. The compact,
16mm wide, design reduces weight and gives
exceptionally high packing density.
♦♦ System backplanes with bussed
power and safe-area connections
♦♦ Custom-designed backplanes for
closest integration into process-
connected systems
♦♦ Compatible with MTL4000 Series
interface family
♦♦ Compact modular design with
‘plug-in’ connections
♦♦ Quick install and release
mechanism
♦♦ High module/channel packing
densities
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 6 487 7887 Fax: +65 6 487 7997
E-mail: enquiry@mtl-inst.com Web site: www.mtl-inst.com
Feb 2007
Product specifications are subject to change without notice
MTL4500
I/O MODULE LIST
DIGITAL INPUT
Part Number Functions
MTL4510 4ch DI solid-state output
MTL4510B 4ch DI multifunction solid-state output
MTL4511 1ch DI relay output
MTL4513 2ch DI solid-state output
MTL4514 1ch DI relay output + LFD alarm
MTL4516 2ch DI relay output
MTL4516C 2ch DI with changeover relay output
MTL4517 2ch DI relay output + LFD alarm
DIGITAL OUTPUT
Part Number Functions
MTL4521 Loop powered solenoid driver
MTL4523 Solenoid driver with LFD
MTL4523R Solenoid driver with LFD
MTL4523L Loop powered solenoid driver + LFD
MTL4524 Switch operated solenoid driver
MTL4524S Switch operated solenoid driver, 24V override
MTL4525 Switch operated solenoid driver low power
ANALOGUE INPUT
Part Number Functions
MTL4541 1ch 2/3 wire Transmitter repeater
MTL4541B 1ch 2/3 wire Transmitter repeater, 2 port isolation
MTL4541P 1ch 2/3 wire Transmitter repeater, high power
MTL4544 2ch 2/3 wire Transmitter repeater
MTL4544B 2ch 2/3 wire Transmitter repeater, 2 port isolation
ANALOGUE OUTPUT
Part Number Functions
MTL4546 1ch 4-20mA smart isolating driver + LFD
MTL4546C 1ch 4-20mA smart isolating driver + oc LFD
MTL4549 2ch 4-20mA smart isolating driver + LFD
MTL4549C 2ch 4-20mA smart isolating driver + oc LFD
�
�
TEMPERATURE INPUT
Part Number Functions
MTL4575 Temperature converter
GENERAL
Part Number Functions
MTL4599 Dummy isolator
MTL4599N General purpose feed-through module
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 6 487 7887 Fax: +65 6 487 7997
E-mail: enquiry@mtl-inst.com Web site: www.mtl-inst.com
Feb 2007
Product specifications are subject to change without notice EPS4510-1
MTL4510 SWITCH/
PROXIMITY DETECTOR
INTERFACE
four-channel, digital input
Hazardous area
Safe area
� � � � � � � � � �
� � � � �
���� �� ��
���
���
�
�������
���� ����
�
� � �
���� ����
� ��
���
�
��
���
�
��
�������
� � �
The MTL4510 enables four solid-state outputs in the safe area to be
controlled by up to four switches or proximity detectors located in a
hazardous area. Each pair of output transistors shares a common
terminal and can switch +ve or –ve polarity signals. A range of
module configurations is available (see Table 1) through the use of
selector switches. When proximity detector modes are selected, LFD is
enabled and the output switches to OFF if a line fault is detected.
SPECIFICATION
See also common specification
Number of channels
4, configured by switches
Location of switches
Zone 0, IIC, T6 hazardous area
Div 1, Group A hazardous location
Location of proximity detectors
Zone 0, IIC, T4-6 hazardous area if suitably certified
Div 1, Group A, hazardous location
Hazardous-area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for
proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1k: ±10%
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2k: in input circuit)
Outputs open if input < 1.2mA (> 10k: in input circuit)
Hysteresis: 200µA (650:) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit.
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100:
Short-circuit alarm off if Rin > 360:
Note: Resistors must be fitted when using the LFD facility with a contact input
500: to 1k: in series with switch
20k: to 25k: in parallel with switch
Safe-area outputs
Floating solid-state outputs compatible with logic circuits
Operating frequency: dc to 500Hz
Max. off-state voltage: ± 35V
Max. off-state leakage current: ± 50µA
Max. on-state resistance: 65:
Max. on-state current: ± 50mA
LED indicators
Green: power indication
Yellow: four: indicates output active
Red: indicates line fault + faulty channel’s yellow LED flashes
Maximum current consumption
40mA at 24V (with all output channels energised)
Power dissipation within unit
0.96W at 24V
Safety description (each channel)
Vo=10.5V Io=14mA Po=37mW Um = 253V rms or dc
Terminal Function
1 Input channel A
2 Input channel AB common (+)
3 Input channel B
4 Input channel C
5 Input channel CD common (+)
6 Input channel D
7 Output channel 1
8 Output channel 1/2 common
9 Output channel 2
10 Output channel 3
11 Output channel 3/4 common
12 Output channel 4
13 Supply –ve
14 Supply +ve
Table 1 - Mode options
See Instruction Manual INM4500 for further mode information.
MODE o/p 1 o/p 2 o/p 3 o/p 4
0 chA chB chC chD
1 chA rev. chB chC chD
2 chA chB rev. chC chD
3 chA chB chC rev. chD
4 chA chB chC chD rev.
5 chA rev. chB chC rev. chD
6 chA chB rev. chC chD rev.
7 chA rev. chB rev. chC rev. chD rev.
8 chA chB chC chD
9 chA rev. chB chC chD
10 chA chB rev. chC chD
11 chA chB chC rev. chD
12 chA chB chC chD rev.
13 chA rev. chB chC rev. chD
14 chA chB rev. chC chD rev.
15 chA rev. chB rev. chC rev. chD rev.
i/p type
switch
prox.
detector
+ LFD
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 6 487 7887 Fax: +65 6 487 7997
E-mail: enquiry@mtl-inst.com Web site: www.mtl-inst.com
Feb 2007
Product specifications are subject to change without notice EPS4510B - 1
MTL4510B SWITCH/
PROXIMITY DETECTOR
INTERFACE
four-channel, multi-function, digital input
Hazardous area
Safe area
� � � � � � � � � �
� � � � �
���� �� ��
���
���
�
�������
���� ����
�
� � �
���� ����
� ��
���
�
��
���
�
��
�������
� � �
The MTL4510B enables four solid-state outputs in the safe area to be
controlled by up to four switches or proximity detectors located in a
hazardous area. Each pair of output transistors shares a common
terminal and can switch +ve or –ve polarity signals. A range of
module configurations is available (see Table 1) through the use of
selector switches. These include start/stop operations and pulse output
modes.
SPECIFICATION
See also common specification
Number of channels
4, configured by switches
Location of switches
Zone 0, IIC, T6 hazardous area
Div 1, Group A hazardous location
Location of proximity detectors
Zone 0, IIC, T4-6 hazardous area if suitably certified
Div 1, Group A, hazardous location
Hazardous-area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for
proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1k: ±10%
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2k: in input circuit)
Outputs open if input < 1.2mA (> 10k: in input circuit)
Hysteresis: 200µA (650:) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit.
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100:
Short-circuit alarm off if Rin > 360:
Note: Resistors must be fitted when using the LFD facility with a contact input
500: to 1k: in series with switch
20k: to 25k: in parallel with switch
Safe-area outputs
Floating solid-state outputs compatible with logic circuits
Operating frequency: dc to 500Hz
Max. off-state voltage: ± 35V
Max. off-state leakage current: ± 50µA
Max. on-state resistance: 65:
Max. on-state current: ± 50mA
LED indicators
Green: power indication
Yellow: four: indicates output active
Red: LFD indication + faulty channel’s yellow LED flashes
Maximum current consumption
40mA at 24V (with all output channels energised)
Power dissipation within unit
0.96 W at 24V
Safety description (each channel)
Vo=10.5V Io=14mA Po=37mW Um = 253V rms or dc
Terminal Function
1 Input channel A
2 Input channel AB common (+)
3 Input channel B
4 Input channel C
5 Input channel CD common (+)
6 Input channel D
7 Output channel 1
8 Output channel 1/2 common
9 Output channel 2
10 Output channel 3
11 Output channel 3/4 common
12 Output channel 4
13 Supply –ve
14 Supply +ve
Table 1 - Mode options
See Instruction Manual INM4500 for further mode information.
MODE Function Equivalent
0 4-ch switch input, MTL4510
1 2-ch each channel one input, two outputs MTL4016
2 Same as mode 1 with phase reversed MTL4016
3 2-ch, 2-pole changeover output
4 1-ch with line fault output MTL4014
5 As mode 4 with changeover outputs
6 1-ch with start-stop latch MTL2210B
7 4-ch switch input, MTL4510
8 4-ch switch input, MTL4510
9 2-ch with line fault output MTL4017
10 As mode 9 with LFD changeover
11 As mode 10 with phase reversed
12 3-ch with normally-open LFD output
13 3-ch with normally-closed LFD output
14 2-ch monostable, pulse stretcher
15 4-ch switch input MTL4510
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 6 487 7887 Fax: +65 6 487 7997
E-mail: enquiry@mtl-inst.com Web site: www.mtl-inst.com
Feb 2007
Product specifications are subject to change without notice
MTL4511 SWITCH/
PROXIMITY DETECTOR
INTERFACE
single channel, with line fault detection
The MTL4511 enables a safe-area load to be controlled by a switch
or proximity detector located in a hazardous-area. When selected,
open or short circuit conditions in the field wiring are detected by the
line-fault-detect (LFD) facility and also indicated on the top of the
module. Phase reversal for the channel is selected by a switch on the
side of the module and output is provided by changeover relay
contacts.
SPECIFICATION
See also common specification
Number of channels
One
Location of switches
Zone 0, IIC, T6 hazardous area
Div. 1, Group A hazardous location
Location of proximity detector
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Hazardous-area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for
proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1k: ±10%
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2k: in input circuit)
Outputs open if input < 1.2mA (> 10k: in input circuit)
Hysteresis: 200µA (650:) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. A line fault is
indicated by an LED. The channel output relay is de-energised if
an input line fault is detected.
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100:
Short-circuit alarm off if Rin > 360:
Note: Resistors must be fitted when using the LFD facility with a contact input
500: to 1k: in series with switch
20k: to 25k: in parallel with switch
Safe-area output
Single pole relay with changeover contacts
Note: reactive loads must be adequately suppressed
Relay characteristics
Response time: 10ms maximum
Contact rating: 10W, 0.5A, 35V dc
LED indicators
Green: power indication
Yellow: channel status, on when output is energised
Red: LFD indication, on when line fault is detected
Maximum current consumption
30mA at 24V
Power dissipation within unit
0.72W at 24V
Safety description (each channel)
Vo=10.5V Io=14mA Po=37mW Um = 253V rms or dc
Hazardous area
� �
� � � � � � � � � �
� � � � �
���� �� ��
���
���
�
�������
�� �
�
�
!��"!#�$%&���'$% %($��$�$���&
)*+���,�-�$��$���&�
&$.�+&$�&$�+���&�
+/�#0��+���$'$��$�
������
Safe area
EPS4511-1
Terminal Function
1 Input –ve
2 Input +ve
3 To earth leakage detector
7 Output normally-open contact
8 Common
9 Output normally-closed contact
13 Supply –ve
14 Supply +ve
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 6 487 7887 Fax: +65 6 487 7997
E-mail: enquiry@mtl-inst.com Web site: www.mtl-inst.com
Feb 2007
Product specifications are subject to change without notice EPS4513-1
The MTL4513 enables two solid-state outputs in the safe area to be
controlled by two switches or proximity detectors located in the
hazardous area. The Ch1/Ch2 output transistors share a common
terminal and can switch +ve or -ve polarity signals. Independent
output phase reversal and line fault detection are enabled via switches
for each output. LFD indication is provided on the top of the module.
SPECIFICATION
See also common specification
Number of channels
Two
Location of switches
Zone 0, IIC, T6 hazardous area
Div. 1, Group A hazardous location
Location of proximity detectors
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Hazardous-area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for
proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1k: ±10%
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2k: in input circuit)
Outputs open if input < 1.2mA (> 10k: in input circuit)
Hysteresis: 200µA (650:) nominal
Line fault detection (LFD) (when selected)
User-selectable for each channel via switches on the side of the
unit. Line faults are indicated by an LED for each channel.
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100:
Short-circuit alarm off if Rin > 360:
Note: Resistors must be fitted when using the LFD facility with a contact input
500: to 1k: in series with switch
20k: to 25k: in parallel with switch
Phase reversal
Independent for each channel, user-selectable
Safe-area outputs
Floating solid-state outputs compatible with logic circuits
Operating frequency: dc to 1kHz
Max. off-state voltage: ± 35V
Max. off-state leakage current: ± 50µA
Max. on-state resistance: 65:
Max. on-state current: ± 50mA
MTL4513 SWITCH/
PROXIMITY DETECTOR
INTERFACE
two-channel, with line fault detection
and phase reversal
Hazardous area
Safe area
� � � �
� � � � � � � � � �
� � � � �
���� �� ��
���
���
�
�������
����
���� ����
����
�� �
�
�
�� �
�
�
!��"!#�$%&���'$% %($��$�$���&
)*+���,�-�$��$���&�
&$.�+&$�&$�+���&�
+/�#0��+���$'$��$�
LED indicators
Green: power indication
Yellow: two: channel status, on when outputs are on
Red: two: LFD indication, on when line fault detected
Maximum current consumption
30mA at 24V
Power dissipation within unit
0.9W typical at 24V with 10mA loads-
1.2W max. with 50mA loads
Safety description (each channel)
Vo=10.5V Io=14mA Po=37mW Um = 253V rms or dc
Terminal Function
1 Input –ve (Ch 1)
2 Input +ve (Ch 1)
4 Input –ve (Ch 2)
5 Input +ve (Ch 2)
6 To earth leakage detector
7 Output (Ch 1)
8 Output (Ch 1/Ch 2)
9 Output (Ch 2)
13 Supply –ve
14 Supply +ve
EUROPE (EMEA) Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
AMERICAS Tel: +1 603 926 0090 Fax: +1 603 926 1899
ASIA PACIFIC Tel: +65 6 487 7887 Fax: +65 6 487 7997
E-mail: enquiry@mtl-inst.com Web site: www.mtl-inst.com
Feb 2007
Product specifications are subject to change without notice EPS4514-2
MTL4514 SWITCH/
PROXIMITY DETECTOR
INTERFACE
single channel with line fault detection
and phase reversal
The MTL4514 enables a safe–area load to be controlled, through a
relay, by a proximity detector or switch located in a hazardous area.
Line faults are signalled through a separate relay and indicated on the
top of the module. Switches are provided to select phase reversal and
to enable the line fault detection.
SPECIFICATION
See also common specification
Number of channels
One
Location of switch
Zone 0, IIC, T6 hazardous area
Div.1, Group A, hazardous location
Location of proximity detector
Zone 0, IIC, T4–6 if suitably certified
Div.1, Group A, hazardous location
Hazardous–area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for
proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1k: ±10%
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2k: in input circuit)
Outputs open if input < 1.2mA (> 10k: in input circuit)
Hysteresis: 200µA (650:) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. Line faults
are indicate