10开式循环冷却水泵控调试试验记录表TSC-10Saudi Rabigh 2×660MW UNIT 1(660MW) SCS COMMISSIONING RECORD
NO:TSC-10 CODE:YD.Rabigh.TS.RK /JL/FB/TSC10
工程名称
NAME
沙特Rabigh 2×660MW #1机
Saudi Rabigh
2×660MW UNIT 1
试运阶段
PHASE
分部试运
T...
Saudi Rabigh 2×660MW UNIT 1(660MW) SCS COMMISSIONING RECORD
NO:TSC-10 CODE:YD.Rabigh.TS.RK /JL/FB/TSC10
工程名称
NAME
沙特Rabigh 2×660MW #1机
Saudi Rabigh
2×660MW UNIT 1
试运阶段
PHASE
分部试运
TRIAL-RUN
专业名称
PROFESSION
热控专业
I&C
项目名称
NAME
开式循环冷却水系统试验纪录表
ACW SYSTEM TEST RECORD
NO.
COMMISSIONING CONTENT
RESULT
REMARK
1
开式循环冷却水泵A 10PCB20AP001
ACW PUMP A
YD.Rabigh.TS.RK /JL/FB/TSC10-001
2
开式循环冷却水泵B 10PCB10AP001
ACW PUMP B
YD.Rabigh.TS.RK /JL/FB/TSC10-002
3
开式循环冷却水泵 A入口电动门
ACW PUMP A INLET MOV 10PCB14AA001
YD.Rabigh.TS.RK /JL/FB/TSC10-003
4
开式循环冷却水泵A出口电动门
ACW PUMP A OUTLET MOV 10PCB14AA002
YD.Rabigh.TS.RK /JL/FB/TSC10-004
5
开式循环冷却水泵 B入口电动门
ACW PUMP B INLET MOV 10PCB10AA003
YD.Rabigh.TS.RK /JL/FB/TSC10-005
6
开式循环冷却水泵B出口电动门
ACW PUMP B OUTLET MOV 10PCB10AA002
YD.Rabigh.TS.RK /JL/FB/TSC10-006
7
8
9
10
11
12
13
14
施工部门: 调试部门: 运行部门:
SEPCOⅢ: COMMISSIONING: OPERATION:
开式循环冷却水泵系统试验
表
ACW SYSTEM TEST RECORD
NAME:ACW PUMP A CODE:YD.Rabigh.TS.RK /JL/FB/TSC10-001
NO.
CONTENT
RESULT
REMARK
TEST
CONDITION
a、运行人员对相关系统检查完成并正常
a、Operators have finished systems checking and the systmes is in normal operation
b、DCS相关硬件、软件工作正常
b、DCS handwares and software are in normal operation
1
START
PERMIT
(AND)
a、开式循环冷却水泵A轴承温度正常<90
a、Open Cycle Cooling Water Pump A Bearing Temp<90
b、开式循环冷却水泵A电机轴承温度正常<90
b、Open Cycle Cooling Water Pump A Motor Bearing Temp<90
c、开式循环冷却水泵A电机线圈温度正常<135
c、Open Cycle Cooling Water Pump A Motor Wind Temp<135
d、开式循环冷却水泵A入口电动门已开
d、Open Cycle Cooling Water Pump A Inlet Motor Butterfly Valve opened
e、开式循环冷却水泵A出口电动门全关或泵投备用
e、Open Cycle Cooling Water Pump A Outlet Motor Butterfly Valve closed Or PUMP INTERLOCK INPUT
f、A电动滤水器前后电动门全开或B电动滤水器前后电动门全开
f、Water system OK ,Inlet water side open(Motor Filter A Inlet/Outlet Motor Butterfly Valve open Or Motor Filter B Inlet/Outlet Motor Butterfly Valve open)
无跳闸条件
h、任一循环水泵运行
h、Any CWP Running
2
STOP
PERMIT
连锁未投入OR 联启条件没来
3
INTERLOCK
START
(OR)
泵联锁投入且开式循环冷却水泵B运行且开式泵出口母管压力<0.12MPA,延时2秒
a、PUMP INTERLOCK INPUT AND ACW PUMP B RUNNING AND ACW PUMP OUTLET HEADER PRESS LOW<0.15MPA(DON 2s)
b、泵联锁投入且开式循环冷却水泵B停运
b、PUMP INTERLOCK INPUT AND ACW PUMP B STOPPED
4
INTERLOCK
STOP
(OR)
a、开式循环冷却水泵A轴承温度>95
a、Open Cycle Cooling Water Pump A Bearing Temp>95
b、开式循环冷却水泵A电机轴承温度>95
b、Open Cycle Cooling Water Pump A Motor Bearing Temp>95
c、开式循环冷却水泵A电机线圈温度>140
c、Open Cycle Cooling Water Pump A Motor Wind Temp>140
d、开式循环冷却水泵A运行延时3s 入口蝶阀关。
d、Open Cycle Cooling Water Pump A running, Inlet Hydraulic Butterfly Valve closed, with 3s delay
e、开式循环冷却水泵A运行延时15s,出口蝶阀关
e、Open Cycle Cooling Water Pump A running with 15s delay, Outlet Hydraulic Butterfly Valve closed
f、所有循环水泵停运延时2秒
f、All CWP Tripped DON 2 S
开式循环冷却水泵系统试验记录表
ACW SYSTEM TEST RECORD
NAME:ACW PUMP B CODE:YD.Rabigh.TS.RK /JL/FB/TSC10-002
NO.
CONTENT
RESULT
REMARK
TEST
CONDITION
a、运行人员对相关系统检查完成并正常
a、Operators have finished systems checking and the systmes is in normal operation
b、DCS相关硬件、软件工作正常
b、DCS handwares and software are in normal operation
1
START
PERMIT
(AND)
a、开式循环冷却水泵B轴承温度正常<90
a、Open Cycle Cooling Water Pump B Bearing Temp<90
b、开式循环冷却水泵B电机轴承温度正常<90
b、Open Cycle Cooling Water Pump B Motor Bearing Temp<90
c、开式循环冷却水泵B电机线圈温度正常<135
c、Open Cycle Cooling Water Pump B Motor Wind Temp<135
d、开式循环冷却水泵B入口电动门已开
d、Open Cycle Cooling Water Pump B Inlet Motor Butterfly Valve opened
e、开式循环冷却水泵B出口电动门全关或泵投备用
e、Open Cycle Cooling Water Pump B Outlet Motor Butterfly Valve closed Or PUMP INTERLOCK INPUT
f、A电动滤水器前后电动门全开或B电动滤水器前后电动门全开
f、Water system OK ,Inlet water side open(Motor Filter A Inlet/Outlet Motor Butterfly Valve open Or Motor Filter B Inlet/Outlet Motor Butterfly Valve open)
无跳闸条件
h、任一循环水泵运行
h、Any CWP Running
2
STOP
PERMIT
连锁未投入OR 联启条件没来
3
INTERLOCK
START
(OR)
泵联锁投入且开式循环冷却水泵A运行且开式泵出口母管压力<0.12MPA,延时2秒
a、PUMP INTERLOCK INPUT AND ACW PUMP A RUNNING AND ACW PUMP OUTLET HEADER PRESS LOW<0.15MPA(DON 2s)
b、泵联锁投入且开式循环冷却水泵A停运
b、PUMP INTERLOCK INPUT AND ACW PUMP A STOPPED
4
INTERLOCK
STOP
(OR)
a、开式循环冷却水泵B轴承温度>95
a、Open Cycle Cooling Water Pump B Bearing Temp>95
b、开式循环冷却水泵B电机轴承温度>95
b、Open Cycle Cooling Water Pump B Motor Bearing Temp>95
c、开式循环冷却水泵B电机线圈温度>140
c、Open Cycle Cooling Water Pump B Motor Wind Temp>140
d、开式循环冷却水泵B运行,延时3s,入口蝶阀关
d、Open Cycle Cooling Water Pump B running, Inlet Hydraulic Butterfly Valve closed, with 3s delay
e、开式循环冷却水泵B运行延时15s,出口蝶阀关
e、Open Cycle Cooling Water Pump B running with 15s delay, Outlet Hydraulic Butterfly Valve closed
f、所有循环水泵停运延时2秒
f、All CWP Tripped DON 2 S
开式循环冷却水泵系统试验记录表
ACW SYSTEM TEST RECORD
NAME:ACW PUMP A INLET MOV CODE:YD.Rabigh.TS.RK /JL/FB/TSC10-003
NO.
CONTENT
RESULT
REMARK
TEST
CONDITION
a、运行人员对相关系统检查完成并正常
a、Operators have finished systems checking and the systmes is in normal operation
b、DCS相关硬件、软件工作正常
b、DCS handwares and software are in normal operation
1
OPEN
PERMIT
2
CLOSE
PERMIT
a、开式循环冷却水泵A停止
a、ACW PUMP A STOPPED
3
INERLOCK
OPEN
(OR)
开式循环冷却水泵A运行
a、ACW PUMP A RUNNING
A泵联锁投入
b、ACW PUMP A INTERLOCK INPUT
4
INTERLOCK
CLOSE
开式循环冷却水泵A跳闸
a、ACW PUMP A TRIPPED
开式循环冷却水泵系统试验记录表
ACW SYSTEM TEST RECORD
NAME:ACW PUMP A OUTLET MOV CODE:YD.Rabigh.TS.RK /JL/FB/TSC10-004
NO.
CONTENT
RESULT
REMARK
TEST
CONDITION
a、运行人员对相关系统检查完成并正常
a、Operators have finished systems checking and the systmes is in normal operation
b、DCS相关硬件、软件工作正常
b、DCS handwares and software are in normal operation
1
OPEN
PERMIT
2
CLOSE
PERMIT
a、开式循环冷却水泵A停止
a、ACW PUMP A STOPPED
3
INERLOCK
OPEN
(OR)
开式循环冷却水泵A运行
a、ACW PUMP A RUNNING
A泵联锁投入
b、ACW PUMP A INTERLOCK INPUT
4
INTERLOCK
CLOSE
开式循环冷却水泵A跳闸
a、ACW PUMP A TRIPPED
开式循环冷却水泵系统试验记录表
ACW SYSTEM TEST RECORD
NAME:ACW PUMP B INLET MOV CODE:YD.Rabigh.TS.RK /JL/FB/TSC10-005
NO.
CONTENT
RESULT
REMARK
TEST
CONDITION
a、运行人员对相关系统检查完成并正常
a、Operators have finished systems checking and the systmes is in normal operation
b、DCS相关硬件、软件工作正常
b、DCS handwares and software are in normal operation
1
OPEN
PERMIT
2
CLOSE
PERMIT
a、开式循环冷却水泵B停止
a、ACW PUMP B STOPPED
3
INERLOCK
OPEN
(OR)
开式循环冷却水泵B运行
a、ACW PUMP B RUNNING
B泵联锁投入
b、ACW PUMP B INTERLOCK INPUT
4
INTERLOCK
CLOSE
开式循环冷却水泵B跳闸
a、ACW PUMP B TRIPPED
开式循环冷却水泵系统试验记录表
ACW SYSTEM TEST RECORD
NAME:ACW PUMP B OUTLET MOV CODE:YD.Rabigh.TS.RK /JL/FB/TSC10-006
NO.
CONTENT
RESULT
REMARK
TEST
CONDITION
a、运行人员对相关系统检查完成并正常
a、Operators have finished systems checking and the systmes is in normal operation
b、DCS相关硬件、软件工作正常
b、DCS handwares and software are in normal operation
1
OPEN
PERMIT
2
CLOSE
PERMIT
a、开式循环冷却水泵B停止
a、ACW PUMP B STOPPED
3
INERLOCK
OPEN
(OR)
开式循环冷却水泵B运行
a、ACW PUMP B RUNNING
B泵联锁投入
b、ACW PUMP B INTERLOCK INPUT
4
INTERLOCK
CLOSE
开式循环冷却水泵B跳闸
a、ACW PUMP B TRIPPED
9
本文档为【10开式循环冷却水泵控调试试验记录表TSC-10】,请使用软件OFFICE或WPS软件打开。作品中的文字与图均可以修改和编辑,
图片更改请在作品中右键图片并更换,文字修改请直接点击文字进行修改,也可以新增和删除文档中的内容。
[版权声明] 本站所有资料为用户分享产生,若发现您的权利被侵害,请联系客服邮件isharekefu@iask.cn,我们尽快处理。
本作品所展示的图片、画像、字体、音乐的版权可能需版权方额外授权,请谨慎使用。
网站提供的党政主题相关内容(国旗、国徽、党徽..)目的在于配合国家政策宣传,仅限个人学习分享使用,禁止用于任何广告和商用目的。