1
VSC-HVDC System Protection:
A Review of Current Methods
Jared Candelaria, Student Member, IEEE, and Jae-Do Park, Member, IEEE
Abstract—Currently classical thyristor-based high voltage di-
rect current (HVDC) systems hold the market in bulk power
transmission. However, recent advances in semiconductor tech-
nology have led to voltage source converter based HVDC (VSC-
HVDC) systems becoming a viable competitor. Not only is VSC-
HVDC a competitor for transmission but it can also be used in
multi-terminal systems, which have become an attractive option
for renewable energy applications or for distribution in large
cities. As more and more VSC-HVDC systems are installed,
the protection of these systems must be taken into account.
This paper explores different options and ideas for VSC system
protection.
Index Terms—HVDC, VSC, Protection
I. INTRODUCTION
Recently voltage source converter based high voltage di-
rect current (VSC-HVDC) systems are becoming more of a
competitor of classical thyristor-based HVDC systems [1]. As
the converter power rating increases it may one day replace
thyristor-based HVDC. VSC-HVDC is attractive because, un-
like classical-HVDC, no reactive power support is needed to
operate the system. In fact VSC’s can produce reactive power,
and control active and reactive power independently [2]. This
controllability allows VSC-HVDC converters to operate in
systems with little or no AC support, something that classical
HVDC cannot achieve without expensive support [3]–[6].
VSC’s are also advantageous in multi-terminal systems. Multi-
terminal systems consist of three or more converters to create
a HVDC network. Applications of multi-terminal systems
include distribution into large cities, renewable energy inter-
connects, and even ship power systems [7]–[10]. VSC’s are
better suited for multi-terminal systems as the power flow can
be changed by changing the direction of the current. Classical
HVDC requires the DC voltage polarity to be changed, which
can be difficult [3], [11], [12].
Currently, all of the installed VSC-HVDC systems are either
back-to-back converters or are connected through underground
cable. No overhead DC lines have been installed as of yet. It
is said that the absence of overhead DC greatly reduces the
risk of DC faults. However, in the case of a cable-connected
system, a ground fault is almost always permanent, either by
the failed cable insulation or the cable damage by an outside
source. As more of these systems are installed into the bulk
power system, protection of the VSC-HVDC systems must be
a priority. VSC-HVDC systems are, by design, vulnerable to
faults on the DC systems. Classical current-sourced-converter-
based (CSC) HVDC naturally are able to withstand short
circuit currents due the DC inductors limiting the current
during fault conditions [8], [13]. When a fault occurs on the
DC side of a VSC-HVDC system the IGBT’s lose control and
Fig. 1. VSC Operation (a) Normal. (b) Positive Line-to-Ground Fault.
the freewheeling diodes act a bridge rectifier and feed the fault
[7], [9], [10], [13]–[17], as shown in Fig. 1. The types of faults
possible on a HVDC system are as follows.
• Positive line to ground fault
• Negative line to ground fault
• Positive line to negative line fault
• Overcurrent
• Overvoltage
A challenge associated with the protection of VSC-HVDC
systems is that the fault current must be detected and extin-
guished very quickly as the converters fault withstand rating
is generally only twice the converter full load rating [10].
Fault detection is also important, especially on multi terminal
systems, in order to isolate the fault and restore the system to
working order. This paper attempts to review the issues and
the current methods of VSC-HVDC protection.
II. POSSIBLE FAULTS
A. Line-to-Ground
A line-to-ground fault (ground fault) occurs when the pos-
itive or negative line is shorted to ground. In overhead lines
faults may occur when lightning strikes the line. This may
cause the line to break, fall to the ground and create fault. In
this situation the fault is always permanent and the line must
be isolated for repair. Ground faults may also occur by objects
falling onto the line, such as trees, providing a path to ground.
In some cases when an object causes the ground fault it may
fall away from the line and the system can be restored. If the
fault persists the line would have to be taken out of service
until the fault path can be cleared.
2
Underground cable is almost completely immune to line-
to-line faults, as insulation, conduit and the earth separate
the cables. However, they can still occur. The insulation of
the cable can fail due to improper installation, excessive
voltage/current, exposure to the environment(water, soil, etc)
or cable aging [13]. When this occurs, the broken insulation
will allow a path for current to flow to ground. As the fault
persists the integrity of the insulation is reduced causing the
fault to worsen. A ground fault may also occur when a person
inadvertently cuts through one of the lines. This can happen
during construction projects. In either case the fault will
always be permanent and will require a complete shutdown
of the line as well as a costly repair.
When a line-to-ground fault occurs, the faulted pole rapidly
discharges capacitor to ground. This causes an imbalance of
the DC link voltage between the positive and negative poles.
As the voltage of the faulted line begins to fall, high currents
flow from the capacitor as well as the AC grid. These high
currents may damage the capacitors and the converter [16].
B. Line-to-Line
As stated before, a line-to-line fault on a cable-connected
system is less likely to occur on the cable. In an overhead
system, line-to-line faults can be caused by an object falling
across the positive and negative line, they may also occur in
the event of the failure of a switching device causing the lines
to short. A switching fault, which is independent of how the
converter stations are connected together, causes the positive
bus to short to the negative bus inside the converter. A line-
to-line fault may be either temporary or permanent.
C. Overcurrent
While overcurrent protection is important during line-to-
line and line-to-ground faults, it must also operate when the
system is being overloaded. Overload conditions may occur in
two-terminal systems when the load increases past the rating
of the converter or as a result of a fault on another part
of the system. For example, if three VSC’s are feeding a
common load and one VSC is dropped due to a permanent
fault, the remaining two must supply the load. This will result
in elevated currents that may overload the converters. In this
situation the overcurrent protection would need to operate.
Another option to avoid a wide spread blackout would be to
shed non-critical loads.
D. Overvoltage
Overvoltages may occur in overload or in fault conditions.
Overvoltages are only a concern during line-to-ground faults.
When the fault occurs, the capacitor discharges rapidly to
ground. The current flows through the ground then back to
the unfaulted line and finally back to the source, which causes
the voltage on the healthy pole to increase to 2 p.u. [16].
Overvoltage is also a concern during the loss of a converter.
The loss of an inverter can cause voltage spikes due to
excessive power, quickly charging the DC link capacitors. A
rectifier loss is only of concern when the loss is temporary.
When the rectifier returns suddenly it can cause overvoltages
similar to that of an inverter loss [18].
Unbalanced AC network phases, mainly caused by faults,
can lead to adverse effects on the operation of the VSC [19].
The configuration of the transformer linking the VSC to the
AC grid can affect the voltage level on the DC side under
AC faults. It can be seen that when the VSC is connected in a
Y/∆,that a ground fault on the AC can result in an overvoltage
of 1.5 p.u. [20].
III. DC PROTECTION WITH AC DEVICES
Protection of DC systems can be done with conventional AC
devices such as circuit breakers and fuses. The advantages of
using AC devices include:
• Less expensive than DC counterparts
• Shorter lead time
• Mature science
• More familiar devices
Below the methods of protection are shown.
A. AC Circuit Breakers
Placing AC circuit breakers on the AC side of the VSC is
the most economical way to protect the DC system. They are
commonly available and can be replaced in a shorter amount
of time. However, AC circuit breakers result in the longest
interruption time as a result of their mechanical restrictions
[7]. Currently, the best interrupting time for an AC circuit
breaker is two cycles [21].
When using an AC circuit breaker, the voltage of the DC
capacitors will be monitored as well as the current in each
DC line at each converter. These values will be fed back to a
standard relay, which will monitor over/undervoltage, as well
as overcurrent. When a DC fault occurs, the capacitors will
discharge rapidly causing the voltage to decrease. The current
on the faulted line will increase over the rated value. Once the
relay senses one or more of these conditions, it will trip the
breaker. In an attempt to restore the system, the relay will enter
a re-closing cycle in which the relay will close back in and
sense the voltage and current of the DC system. If the fault is
cleared the system will return to normal, but if a permanent
fault is detected the relay will lock out the breaker. The relay
identifies a permanent fault by the re-closing sequence. A
typical industry standard for re-closing on AC systems is that
two attempts will be made; this can be applied to the VSC
systems as well. After two attempts without success, the relay
determines that the fault is permanent and will not allow the
breaker to close.
In back-to-back or two-terminal transmission systems, dif-
ferential protection may be used to protect each converter,
as shown in Fig. 2. The differential relay (Note: 87 is the
ANSI standard number for a differential relay) will measure
the current entering the converter as well as the current leaving
the converter. If the current entering does not match the current
leaving the differential relay, it will trip the AC breaker [22],
[23]. In back-to-back systems one relay could also monitor the
AC current at the sending VSC as well as the receiving VSC.
If the current at one end does not match the current at the
3
Fig. 2. Back to Back Differential Protection.
Fig. 3. Two-Terminal Differential Protection
other end, the relay would know a fault has occurred and the
VSC’s would be tripped offline. In a two terminal transmission
system, two relays would be required and the current readings
would have to be sent to the other relay via communication
as can be seen in Fig. 3. This type of differential protection
is common in AC systems [24] as could be applied to VSC
protection. Also, compensation for losses would have to be
taken into account.
While AC circuit breakers are inexpensive, easy to use, and
widely used, they also shut down the entire converter. This
is problematic in the case of ground faults where the faulted
line could be isolated and the system could run mono-polar
using ground as a return path [16]. AC circuit breakers are
also inconvenient in multi-terminal systems, which will be
discussed later.
B. Fuses
Fuses on the AC side are generally not a good solution
for protection of the VSC [25]. This is because a fuse is a
thermal device that is only allowed one operation. Fuses do
not have the ability to distinguish whether a fault is temporary
or permanent. To a fuse every fault is permanent and therefore
the system would not be able to be restored until the fuse was
physically replaced. The only place that a fuse may be an
acceptable alternative is for a non-critical load, or in areas
where space is limited, such as a ship. Fuses are used for
protection [25], but are mainly for AC protection and other
DC devices protect the DC line. The DC devices coordinate
with the fuse such that they will trip before the fuse. The fuse
will only operate in the event that the DC protection fails.
Fig. 4. IGBT-CB Fault Blocking Capabilities.
Overall, fuses should be used only when necessary and all
other options are not possible.
IV. DC PROTECTION WITH DC DEVICES
While AC devices are an economical way to protect the DC
system, DC devices are a better option whenever possible. DC
protective devices can act faster than their AC counterparts,
as well as sectionalize lines. This allows the operation of
unfaulted lines to continue. The methods of protection using
DC devices are shown below.
A. IGBT Circuit Breakers
An IGBT circuit breaker (IGBT-CB) utilizes the blocking
capability of the solid-state device. Like the other IGBTs in the
converters, the IGBT-CBs are configured with an anti-parallel
diode. The only drawback to the IGBT-CB is that it is a uni-
directional device. This is illustrated in Fig. 4. When a fault
occurs on the DC line, the IGBT is able to block the fault
current (represented by the dashed line in Fig. 4). If the fault
occurs on the converter side, the anti-parallel diodes conduct
and allow current to flow (represented by the solid line in Fig.
4). In this scenario the IGBT-CB must rely on the blocking of
the IGBTs in the converter [7].
For two-terminal systems, IGBT-CBs can be placed at each
converter station, one on the positive line and one on the
negative line, as can be seen in Fig. 4. Fast acting DC switches
are used in conjunction with the IGBT-CB, which is used
to isolate the line once the fault current has been cleared. It
should be noted that the switch cannot break current and may
only be opened once the fault has been extinguished. As with
AC, the DC current of each line and the DC voltage of each
capacitor will be sensed. Once the control system senses a
fault on the line, an appropriate IGBT-CB will receive a gate
signal to block the current. Once the fault current has been
extinguished the fast acting DC switches will open, isolating
the line. To determine if the fault is temporary or permanent,
the DC switches and the IGBT-CB will close. If the fault has
cleared the system will return to normal operation. If the fault
is still present, the line will be isolated again and a permanent
fault will be determined.
The advantage of using an IGBT-CB is that the entire
converter is not shutdown in the case of a ground fault. This
4
Fig. 5. ETO Based VSC-HVDC Converter.
allows the faulted line to be isolated and have the system
continue to run mono-polar. The IGBT-CB also opens faster
than its AC counterpart. The disadvantage to the IGBT-CB is
that it cannot protect against DC rail faults in the rectifier [25].
B. Converter Embedded Devices
Converter embedded devices are active, protective compo-
nents that are installed inside a VSC to detect and isolate DC
faults. This method eliminates the use of additional devices,
reducing the footprint of the converter station and also possibly
cutting cost. However, a redesign of the converter is required.
In [10], the converter uses two Emitter Turn Off (ETO) devices
in an anti-parallel configuration to achieve both switching and
protection. The ETO has a higher voltage and current rating
than IGBT. Fig. 5 illustrates the converter configuration. In
normal operation the ETO’s X act as the switching devices,
while ETO’s Y act as the anti-parallel diode, and are constantly
fired on. In the event of a fault the ETO’s X are blocked while
ETO’s Y continue to feed the fault. Once the fault has been
identified as permanent the Y ETO’s will be gated off.
Another protection method has replaced the typical IGBT
and anti-parallel diode is a combination switching device
with the submodule shown in Fig. 6 [6], [17]. The converter
submodule provides two different levels of protection. The
first level protects the converter from being shutdown during
a switching device failure. In the event of a switching device
failure, the submodule will close switch K1, shorting out the
defective submodule. This allows the converter to continue
to operate by using redundant modules for un-altered system
performance. The second level of protection reacts under fault
conditions. As stated earlier, the switching device blocks and
the anti-parallel diode conducts to feed the fault under fault
conditions. The freewheeling diodes in VSC’s are not able to
withstand large surge currents, and may be damaged before the
fault is cleared. The solution in [17] is to bypass the IGBT
and the anti-parallel diode with a press-pack thyristor K2. The
proposed press-pack thyristor is able to withstand high surge
currents, protecting the anti-parallel diode until the fault can
be cleared.
This protection method allows the converter additional con-
trol and increases the current rating of the switching devices.
It also cuts down on the number of components required for
protection because the protection is embedded in the converter.
Fig. 6. VSC-HVDC Converter Submodule.
The disadvantage is that the entire converter must be shut down
in the event of a permanent fault. This works well in two-
terminal systems but may cause problems in multi-terminal
systems.
V. MULTI-TERMINAL SYSTEM PROTECTION
VSC-HVDC systems are very appealing in multi-terminal
systems, as power flow can be changed not by voltage polarity
but the direction of the current. The possible applications
for multi-terminal VSC-HVDC (MT-VSC-HVDC) systems are
used in renewable energy applications and in distribution of
power in mega cities. The protection strategies for MT-VSC-
HVDC utilize both AC and DC protection.
A. AC Protection
As stated previously, DC protection can be achieved by
using AC circuit breakers on the AC systems. This strategy
can be applied to MT-VSC-HVDC as well. A ”hand shaking”
method is proposed in [9]. This method, in addition to using
AC circuit breakers, implements fast acting DC switches. The
switches are only used to isolate lines and cannot break load
or fault current. Each VSC will receive current measurements
from their respective DC switches. When a fault occurs all
of the AC circuit breakers associated with the MT-VSC-
HVDC system will trip. Next, each VSC must determine
which one of its respective switches to open. This is done by
measuring the magnitude and direction of the current through
each switch. The switch that will be selected is the one with
the largest positive fault current. The hand shaking method
defines positive as out of the node and negative into the node.
Fig. 7 illustrates the example system given in [9].
When a fault occurs on Line 1, VSC1 receives current
measurements from SW11 and SW31. VSC1 senses that the
current through SW11 is positive and the current through
SW31 is negative. Through the hand shaking method VSC1
opens SW11. VSC2 receives current measurements from
SW12 and SW22. Once again the current through SW12 is
positive and the current through SW22 is negative and switch
SW12 is selected. VSC3 receives current measurement from
SW33 and SW23. The current direction for both switches is
measured as positive. The switch with the highest magnitude
of current is selected. At this point Line 1, the faulted line, is
isolated, and Line 3 is open at one end. At this point the
system must enter a re-closing mode. First, all of the AC
5
Fig. 7. (a) Current Flow During a Fault. (b) Fault Isolation with the
Hand Shaking Method.
breakers will close back in, re-energizing the VSC’s. Next,
the fast DC switches of the non-faulted DC lines must be
closed. The VSC’s only re-close switches when the voltage of
its respective line is near the voltage of the VSC terminals. Fig.
8 shows the re-closing method presented in [9], where it can
be seen that only SW33 will be able to re-close. During the
fault VSC1 chose to open SW11, leaving SW31 closed. Once
the AC breakers re-close, and the VSC1 is